Product Category

Got any Questions? Call us Today!

+8618758069661

service@fctel.com.cn

Or leave us a message

Online Message

Industrial Din Rail Power Supply(AC220V to DC24V8A (with power factor adjustment))

View : 13
Type :
Description :

Features

●  IP40 protection level, thick heat dissipation aluminum alloy anodized process shell, can withstand the test of harsh environment;

●  With digital tube display voltage, convenient on-site voltage adjustment and service activation.

●  1 power supply specification: 24V8A 192W full power output, small temperature rise.

●  With power factor adjustment (PF), PF>0.9.

●  Designed according to safety regulations, isolation withstand voltage greater than 1500Vac.

●  Designed with reference to EMC requirements, strong anti-interference ability.

●  Complete protection functions: output overcurrent, overload, short circuit protection.

●  Lightning protection function, 6KV lightning protection, can resist inductive high voltage, surge protection, etc.;

●  Fanless and efficient thick heat dissipation aluminum alloy heat dissipation, reducing repair time;

●  IP40 shell protection level, can withstand the test of harsh environment;

●  DIN 35mm rail or wall-mounted installation;

●  Wide temperature type: working temperature -40℃~ +85℃;

●  Full load high temperature burn-in, 100% aging test;

Parameters

Electrical Parameters & Specifications

Parameter

Model

FCP-2408G

Output

 

 

 

 

 

 

 

 

Voltage

24V

Current

0-8A

Rated Power

192W

Voltage Ripple (noise)

50mVp-p

Power Factor(PF)

≥0.9

Line Regulation

±0.3%

Load Regulation

±1%

Work Efficiency

>=91.7%

Start-up & Rise Time

1500ms,30ms/220Vac;2500ms,50mS/110Vac(At full load)

Input

 

 

 

Voltage Range

90vc–264Vac;127VDC–370VDC

Alternating Current

0.96A/220 volt,1A/110 volt

Frequency Range

47-63Hz

Lightning Strikes & Surge

6KV lightning protection, surge current: cold start <40A/230VAC

Protect

 

 

Output Short Circuit

Hiccup mode, output can be automatically restored after fault is cleared

Output Over Current

Rated output current 130%-200%

Output Overload

Rated output power 130%-200%

Environment

 

 

 

 

 

Operating Temperature

-40℃—+85℃

Working Humidity

20-90% RH (No condensation)

Storage Temperature

-40℃—+85℃

Storage Humidity

10-95% Relative humidity

Vibration

10-500Hz, 2G 10min/cycle, 60min each for X, Y and Z axis

MTBF

>100,000 hours

Specification

 

Dimensions (L x W x H)

133mm*110mm*50mm

Weight

0.96kg

Remark:

1.Unless otherwise specified, all specifications and parameters are measured at 220Vac input, rated load, and 25℃ ambient temperature.
2.Voltage noise measurement method: Use 30cm double-stripe wire to connect 1 0.1uF and 1 47uF capacitor in parallel, and measure with a bandwidth of 20MHz.
3.Accuracy: includes setting error, linear adjustment rate and load regulation
4.Linear regulation rate measurement method: Under the condition of rated output power, adjust the input voltage within the full range and measure the output voltage change rate.
5.Load regulation rate measurement method: Measure the output voltage change rate when the output current is adjusted within the full range.

Product Size

                   

Leave a Message

If you are interested in any product, please contact us. We will introduce our products to you in more detail